Skip to main content
Schneider Electric C60H4P6AD — 2-Pole MCB (DIN Rail)

Schneider C60H4P6AD Miniature Circuit Breaker, D Curve, 6 A,

MPNC60H4P6AD
Obsolete

Schneider Electric Multi9 C60H, miniature circuit breaker, C60H4P6AD, 4P, 6 A, D curve, 10 kA Icn at 230/400 V AC, thermal-magnetic trip, 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60H4P6AD — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60H4P6AD — Electrical
ParameterValue
Rated current [In]6 A at 40 °C
Number of protected poles4
Pole configuration4P
Rated operational voltage [Ue]12...440 V AC 50/60 Hz
Network type (AC/DC)DC AC
Network frequency50/60 Hz
C60H4P6AD — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA conforming to IEC 60947-2 - 400...415 V AC 50/60 Hz
Energy limitation class3 conforming to IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
C60H4P6AD — Mechanical
ParameterValue
9 mm pitches8
Width72 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Terminal tightening torquePower circuit: 2 N.m upside 2 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
C60H4P6AD — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
C60H4P6AD — Approvals
ParameterValue
Standards / complianceIEC 60947-2 EN 60898

Product details

The Schneider Electric C60H4P6AD is a 4-pole miniature circuit breaker from the Multi9 C60 range, rated at 6 A with a D trip curve. Thermal-magnetic trip technology gives you both overload protection (thermal bimetal) and short-circuit protection (magnetic coil) in one unit. Breaking capacity is 10 kA Icn at 230/400 V AC per EN 60898, and under IEC 60947-2 it reaches 15 kA Icu at 400...415 V AC and 30 kA Icu at 230...240 V AC. The 4-pole configuration protects all three phases plus neutral, with suitability for isolation confirmed per IEC 60947-2.

Occupies 8 modules of 9 mm pitch, so it takes 72 mm of rail width. Depth is 73 mm, height 81 mm.

Certified to IEC 60947-2 and EN 60898 — the twin standards for industrial and residential MCBs.

Frequently asked questions

Where can I buy C60H4P6AD and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the closest alternative to C60H4P6AD in the Multi9 family?

Within the same C60 range, the key variant is the C curve version (e.g., C60H4P6AC) which trips magnetically at 5 to 10 x In instead of the D curve's 10 to 14 x In. The D curve is the correct choice for motor and transformer loads with high inrush; the C curve suits general-purpose distribution. No pin-compatible alternative exists — the curve is the selection gate.

What is C60H4P6AD's listed depth?

The depth is 73 mm, with a width of 72 mm (8 x 9 mm pitches) and height of 81 mm.

What compliance documentation does this MCB carry?

Certified to IEC 60947-2 and EN 60898. Tropicalisation class 2 per IEC 60068-1. Suitability for isolation confirmed per IEC 60947-2. Operating and storage temperature ranges are specified per the standards.

MPN
C60H4P6AD