Schneider Electric C60HB110 — 1-Pole MCB (DIN Rail)

C60HB110 C60H MCB, 10A B Curve 1P, Multi9 Range

MPNC60HB110
Obsolete

Schneider Electric Multi9 C60H series, C60HB110 miniature circuit breaker, 1-pole 10 A B-curve, thermal-magnetic trip, 10 kA Icn per EN 60898, 15 kA Icu per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60HB110 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60HB110 — Electrical & Protection
ParameterValue
Rated current (In)10 A
Tripping curve codeB
Breaking capacity (Icu / AIR)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit technologyThermal-magnetic

Product details

The C60HB110 is a 1-pole 10 A miniature circuit breaker from the Schneider Electric Multi9 C60H line. The breaker carries a 10 kA Icn breaking capacity at 230/400 V AC per EN 60898, with higher Icu ratings under IEC 60947-2: 15 kA at 230...240 V AC, 20 kA at 60 V DC (1P), 30 kA at 130 V AC, and 4 kA at 400...415 V AC.

The B curve (3–5× In) is the right match for resistive loads like heaters, lighting, and control transformers — it avoids nuisance trips from small inrush while still clearing low-level faults fast. The 10 A rating protects a 2.5 mm² copper circuit at typical UK domestic and light commercial panel densities. The 10 kA Icn per EN 60898 is the standard service breaking capacity for most distribution boards; the higher Icu ratings under IEC 60947-2 (15–30 kA depending on voltage) give fault-clearing headroom when the breaker is used in industrial switchgear where the prospective short-circuit current is higher. Single-pole construction means it switches only the line conductor — used in single-phase circuits or as a branch protector in three-phase panels where each pole is a separate phase.

Panel integration

The C60H range snaps onto standard DIN rail. The 1P width is 18 mm per pole — the standard modular MCB footprint. Spring-cage terminals accept 1–25 mm² conductors. Busbar comb slots are compatible with the Multi9 pin-and-fork busbar system for commoning the line side across multiple breakers in a distribution board.

Frequently asked questions

What compliance documentation does Schneider provide for C60HB110?

The C60HB110 is certified to EN 60898 (for Icn ratings) and IEC 60947-2 (for Icu ratings). The evidence does not list RoHS, REACH, UL, or other specific compliance documents for this order code. Verify documentation requirements with your local Schneider representative or request a certificate of conformity at quote time.

MPN
C60HB110