Skip to main content
Schneider Electric C60HB150 — 1-Pole MCB (DIN Rail)

C60HB150 C60H MCB, 1P 50A Curve B, 10 kA

MPNC60HB150
Obsolete

Schneider Electric Multi9 C60H series, C60HB150 miniature circuit breaker, 1-pole, 50 A, curve B, 10 kA Icn per EN 60898.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60HB150 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60HB150 — Electrical & Protection
ParameterValue
Rated current (In)50 A
Tripping curve codeB
Breaking capacity (Icu / AIR)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 15 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to IEC 60947-2 30 kA Icu at 130 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit technologyThermal-magnetic

Product details

The C60HB150 is a 1-pole miniature circuit breaker from the Schneider Electric Multi9 C60H series, rated 50 A with a B tripping curve. It uses a thermal-magnetic trip unit and is intended for distribution applications protecting branch circuits against overloads and short circuits.

The breaking capacity is specified under multiple standards and voltage conditions, which matters for selective coordination studies and SCCR compliance. Per EN 60898 it carries 10 kA Icn at 230/400 V AC — this is the service breaking capacity for a domestic or light commercial panel. Under IEC 60947-2 the rated ultimate breaking capacity (Icu) reaches 15 kA at 230–240 V AC, 30 kA at 130 V AC, and 20 kA at 60 V DC (1-pole).

Curve B — what it governs

A B-curve MCB trips magnetically at 3 to 5 times In (150–250 A for this 50 A unit). That characteristic suits resistive or lightly inductive loads — lighting circuits, socket outlets, control transformers — where inrush is modest. For motor-starting or high-inrush loads a C or D curve would be more appropriate to avoid nuisance tripping.

The 1-pole format snaps onto standard DIN rail, occupying one modular pitch (17.5 mm typical). The Multi9 C60H family shares the same footprint as the current Acti9 range, so panel cutouts and busbar layouts designed for C60H breakers remain mechanically compatible. Terminal capacity and torque ratings should be verified against the original installation documentation.

Frequently asked questions

What is the breaking capacity of C60HB150 at 230 V?

Per EN 60898 the C60HB150 carries 10 kA Icn at 230/400 V AC. Under IEC 60947-2 the Icu is 15 kA at 230–240 V AC.

What does curve B mean on this MCB?

Curve B means the magnetic trip operates at 3 to 5 times the rated current (150–250 A for the 50 A C60HB150), making it suitable for resistive and low-inrush loads.

Where can I buy C60HB150?

The C60HB150 is obsolete but can be sourced through independent distribution channels. It is quoted to order against an RFQ — availability and current pricing are confirmed at quote time.

MPN
C60HB150