Skip to main content
Schneider Electric C60HB350 — 2-Pole MCB (DIN Rail)

C60HB350 C60H MCB 3P 50A Curve B, Obsolete

MPNC60HB350
Obsolete

Schneider Electric Multi9 C60H series, C60HB350 miniature circuit breaker, 3P, 50 A, curve B, thermal-magnetic trip, 10 kA Icn at 230/400 V AC (EN 60898).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60HB350 — Identification
ParameterValue
Product nameC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60HB350 — Electrical
ParameterValue
Rated current [In]50 A
Number of protected poles3
Pole configuration3P
C60HB350 — Protection
ParameterValue
Tripping curve codeB
Breaking capacity (Icu)10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Trip unit technologyThermal-magnetic

Product details

The C60HB350 is a 3-pole C60H miniature circuit breaker from the Schneider Electric Multi9 range, rated 50 A with a B-curve trip characteristic. It uses a thermal-magnetic trip unit and is designed for distribution applications. Breaking capacity varies by standard and voltage: 10 kA Icn at 230/400 V AC (EN 60898), and up to 30 kA Icu at 230...240 V AC (IEC 60947-2). For DC applications, it achieves 25 kA Icu at 125 V DC (2P) and 50 kA Icu at 250 V DC (4P).

The 10 kA Icn at 230/400 V AC (EN 60898) is the rated short-circuit capacity for residential/commercial distribution boards; the higher Icu values under IEC 60947-2 (up to 30 kA at 230...240 V AC) apply when the breaker is used in industrial panels with higher prospective fault current. Three protected poles cover three-phase circuits — typical for a 400 V three-phase distribution sub-feed or a three-phase resistive load.

Frequently asked questions

How do I get current pricing and availability for C60HB350?

Submit an RFQ. The part is sourced to order through our independent distribution network, with pricing and stock confirmed at quote time.

What is C60HB350's breaking capacity?

It has a 10 kA Icn at 230/400 V AC conforming to EN 60898, and up to 30 kA Icu at 230...240 V AC conforming to IEC 60947-2. DC ratings go up to 50 kA Icu at 250 V DC (4P).

What is the curve code for C60HB350?

The curve code is B, meaning the magnetic trip operates at 3 to 5 times the rated current (150–250 A for this 50 A breaker).

MPN
C60HB350