Skip to main content
Schneider Electric C60HC125 — 1-Pole MCB (DIN Rail)

Schneider Electric C60HC125 MCB, 1P 25A C-Curve, 10kA, Multi

MPNC60HC125
Obsolete

Schneider Electric Multi9 C60H series, C60HC125 miniature circuit breaker, 1 pole, 25 A, C curve, 10 kA breaking capacity, 230-240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C60HC125 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
C60HC125 — Electrical & Protection
ParameterValue
Rated current (In)25 A at 30 °C
Rated operational voltage (Ue)230...240 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)10 kA AC conforming to BS EN 60898
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
C60HC125 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² stranded
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth70 mm
C60HC125 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...100 °C
IP degree of protectionIP20 IP40
C60HC125 — Approvals
ParameterValue
Conformity standardsAS NZS 60898

Product details

The C60HC125 is a 1-pole miniature circuit breaker from Schneider Electric's Multi9 C60H range, rated 25 A at 30 °C with a C-curve trip characteristic (magnetic trip between 5 and 10 times In). It breaks fault currents up to 10 kA AC per BS EN 60898 and is rated for 230-240 V AC 50/60 Hz circuits. The thermal-magnetic trip unit combines overload and short-circuit protection in a single 18 mm wide DIN-rail module.

Above 30 °C ambient, derate per the thermal curve — the 25 A figure is not valid at 40 °C panel temperature. The C curve (5-10 x In magnetic trip) means it tolerates moderate inrush, typical for mixed resistive and lightly inductive loads like small motor circuits, lighting banks, and control transformers.

Panel Integration & Deployment

The toggle switch provides local ON/OFF indication and manual isolation, with contact position indicator confirming the state.

Frequently asked questions

Where can I buy C60HC125 and how do I get a price?

The C60HC125 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock or price figures are stated here.

What is C60HC125's rated current and breaking capacity?

Rated 25 A at 30 °C with a 10 kA breaking capacity at 230-240 V AC per BS EN 60898. The C curve trips magnetically between 5 and 10 times In.

MPN
C60HC125