Skip to main content
Schneider Electric C60HD206 — 2-Pole MCB (DIN Rail)

C60HD206 Multi9 C60H MCB, 6 A, D Curve, 2P, Obsolete

MPNC60HD206
Obsolete

Schneider Electric Multi9 C60H series, C60HD206, 2-pole miniature circuit breaker, 6 A rated current, D tripping curve, thermal-magnetic, 10 kA breaking capacity.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60HD206 — Identification
ParameterValue
Product nameC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60HD206 — Electrical
ParameterValue
Rated current [In]6 A
Number of protected poles2
Pole configuration2P
C60HD206 — Protection
ParameterValue
Tripping curve codeD
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 25 kA Icu at 125 V DC 2P conforming to EN/IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to EN/IEC 60947-2 50 kA Icu at <= 250 V DC 4P conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic

Product details

The Schneider Electric C60HD206 is a 2-pole miniature circuit breaker from the Multi9 C60H range, rated at 6 A with a D tripping curve and thermal-magnetic trip unit. It's a distribution-grade MCB — the D curve means it's built for loads with high inrush current, like small motors or transformers, where the magnetic trip kicks in at 10 to 14 times the rated current to avoid nuisance trips on startup.

This part is officially obsolete per the manufacturer. If you've got this on a BOM for a panel that's already in the field, you're looking at the surplus or broker channel to source it. No direct factory replacement is listed — the C60H family has been superseded by newer ranges (like the Acti9 iC60 series), but pin-compatibility and footprint should be verified against the specific mounting and busbar arrangement in your existing panel.

Rated breaking capacity hits 10 kA Icu at 440 V AC per EN/IEC 60947-2, and 15 kA at 400–415 V AC — enough for most commercial and light industrial distribution boards. The 2-pole format protects both phase and neutral on a single-phase line, or two phases on a three-phase system where you need independent overcurrent protection per pole. Mounts on standard DIN rail, same as any Multi9 device, so it swaps into an existing C60H panel without re-drilling or re-bussing.

Frequently asked questions

Where can I buy C60HD206?

C60HD206 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send a request and we'll check the market for you.

What is C60HD206's D curve used for?

The D curve on this MCB means the magnetic trip operates at 10 to 14 times the rated current (60–84 A), which suits loads with high startup surges like small motors, transformers, or welding equipment. It avoids nuisance tripping on inrush while still protecting against short circuits.

MPN
C60HD206