Skip to main content
Schneider Electric C60HD210 — 2-Pole MCB (DIN Rail)

C60HD210 C60H MCB 2P 10A D Curve, 10kA at 440V

MPNC60HD210
Obsolete

Schneider Electric Multi9 C60H, C60HD210, 2-pole 10 A D-curve miniature circuit breaker, 10 kA Icu at 440 V AC, thermal-magnetic trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C60HD210 — Identification
ParameterValue
Product nameC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
C60HD210 — Electrical
ParameterValue
Rated current [In]10 A
Number of protected poles2
Pole configuration2P
C60HD210 — Protection
ParameterValue
Tripping curve codeD
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 25 kA Icu at 125 V DC 2P conforming to EN/IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to EN/IEC 60947-2 50 kA Icu at <= 250 V DC 4P conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic

Product details

C60HD210 — obsolete D-curve MCB, last-time-buy sourcing

The C60HD210 is a 2-pole 10 A D-curve miniature circuit breaker from the Schneider Multi9 range, designated C60H. It is now marked obsolete by the manufacturer, so this is a last-time-buy or surplus-channel part — not a current-production SKU.

Breaking capacity and application fit

Breaking capacity is 10 kA Icu at 440 V AC per EN/IEC 60947-2, and 15 kA Icu at 400–415 V AC under the same standard. For domestic/commercial distribution per EN 60898 it carries 10 kA Icn at 230/400 V AC. On the DC side, 25 kA Icu at 125 V DC (2-pole series), stepping up to 40 kA at 125 V DC with 3 poles in series and 50 kA at ≤250 V DC with all 4 poles.

Trip technology and panel integration

Thermal-magnetic trip unit — bimetal element for overload, solenoid for short-circuit. Two protected poles in a 2P form factor. Fill factor is one module per pole — 2 modules wide on the DIN rail.

Frequently asked questions

Where can I buy the C60HD210 and get a price?

The C60HD210 is sourced to order through independent distribution against an RFQ. Because it is obsolete, stock is limited and variable — submit a request for current availability and pricing; both are confirmed at quote time.

What is the C60HD210's D curve used for?

The D curve (10–20× In magnetic trip threshold) is designed for loads with high inrush current — motor starters, transformers, welding equipment, and some LED drivers. It avoids nuisance tripping on startup that a B or C curve would see.

What breaking capacity does the C60HD210 have at 440 V AC?

10 kA Icu at 440 V AC 50/60 Hz per EN/IEC 60947-2. At 400–415 V AC the same standard gives 15 kA Icu. Under EN 60898 it is rated 10 kA Icn at 230/400 V AC.

MPN
C60HD210