Skip to main content
Schneider Electric C6337E570 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C6337E570 MicroLogic 7.3 E Trip Unit, 570

MPNC6337E570
Active

Schneider Electric ComPacT NSX series, MicroLogic 7.3 E electronic trip unit, 570 A at 40 °C, 3P, LSIR protection with integrated earth-leakage, EN/IEC 60947-2.

$22.63Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C6337E570 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C6337E570 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
C6337E570 — Identification
ParameterValue
Product / component typeTrip unit
Product range / familyComPacT
C6337E570 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C6337E570 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

MicroLogic 7.3 E — 570 A electronic trip unit for ComPacT NSX

The Schneider Electric C6337E570 is the MicroLogic 7.3 E electronic trip unit for the ComPacT NSX400...630 molded-case circuit breaker platform. It's rated 570 A at 40 °C and provides LSIR protection — long-time, short-time, instantaneous, and residual (earth-leakage) — all in one programmable package. The trip unit mounts into the fixed ComPacT NSX breaker frame and communicates energy metering, power quality data, and event logs through the integrated LCD display. Built to EN/IEC 60947-2, this is a Class II, pollution degree 3 device suitable for distribution panels and industrial switchboards. The 3-pole, 3D protected design covers all three phases plus neutral for earth-leakage sensing. The 20-minute thermal memory before and after tripping means the trip curve accounts for prior heating — critical for motor and transformer feeders where cumulative thermal stress matters.

Protection and adjustment ranges

The long-time pickup (Ir) adjusts from 250 to 570 A, with delay (Tr) settable 15...400 s at 1.5 x Ir, 0.35...11 s at 7.2 x Ir, or 0.5...16 s at 6 x Ir. Short-time pickup (Isd) spans 1.5 to 10 x Ir, delay (tsd) 0...0.4 s with I²t on or off. Instantaneous pickup (Ii) adjusts 1.5 to 11 x In. The earth-leakage protection is Class A, integrated, and can be disabled via the IΔn rotary switch. The trip unit operates from -25 to 70 °C and stores from -40 to 85 °C. IP40 front protection keeps dust and incidental contact out of the display and settings interface.

Frequently asked questions

What are the key protection functions of the MicroLogic 7.3 E?

The MicroLogic 7.3 E provides LSIR protection: long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and earth-leakage (R) with Class A sensitivity.

What standards does C6337E570 comply with?

The C6337E570 complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear. It is also rated Class II for electrical shock protection and pollution degree 3 per IEC 60947-1.

How do I get current pricing and availability for C6337E570?

The C6337E570 is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current pricing and availability at the time of your order.

MPN
C6337E570