Skip to main content
Schneider Electric C6344A570 — Residual Current Breakers (RCCB/RCBO)

C6344A570 ComPacT NSX MicroLogic 4.3 AL Trip Unit, 570 A

MPNC6344A570
Active

Schneider Electric ComPacT NSX, MicroLogic 4.3 AL electronic trip unit, 570 A, 4P, LSoI protection with integrated earth-leakage (Class A), EN/IEC 60947-2.

$17.26Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C6344A570 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload Color indicator (yellow) for residual current
C6344A570 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
C6344A570 — Identification
ParameterValue
Product / component typeTrip unit
Product range / familyComPacT
C6344A570 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C6344A570 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C6344A570 is a MicroLogic 4.3 AL electronic trip unit for the ComPacT NSX400...630 range, rated 570 A at 40 °C. It provides LSoI protection — long-time overload, short-time short-circuit with fixed delay, and instantaneous short-circuit — with integrated earth-leakage protection (Class A).

Protection and adjustments

Long-time pickup (Ir) is adjustable from 250 to 570 A, with fixed time delays: 400 s at 1.5 x Ir, 16 s at 6 x Ir, and 11 s at 7.2 x Ir. Short-time pickup (Isd) adjusts from 1.5 to 10 x Ir with a fixed delay. Instantaneous pickup (Ii) is fixed at 6900 A. Earth-leakage sensitivity (IΔn) and time delay (Δt) are both adjustable.

The trip unit mounts fixed in a 4-pole ComPacT NSX400...630 breaker frame, neutral on the left. It is rated IP40 (finger-safe) and operates from -25 to 70 °C, storing from -50 to 85 °C. Local signalling includes a green flashing LED for ready, red/orange LEDs for overload at 105% / 90% Ir, and a yellow indicator for residual current.

Frequently asked questions

What is the C6344A570 used for?

It is an electronic trip unit for the ComPacT NSX400...630 range, providing overload, short-circuit, and earth-leakage protection in AC distribution systems.

Where can I buy the C6344A570?

The C6344A570 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What are the key ratings of the C6344A570?

The trip unit is rated 570 A at 40 °C, 440 V AC, 50/60 Hz. It offers adjustable long-time pickup (250–570 A), short-time pickup (1.5–10 x Ir), and fixed instantaneous pickup at 6900 A, with integrated earth-leakage protection (Class A).

MPN
C6344A570