Skip to main content
Schneider Electric C63H44V570 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C63H44V570 ComPacT NSX630H, 570 A, 100 kA

MPNC63H44V570
Active

Schneider Electric ComPacT NSX, NSX630H, 4P, 570 A at 40 °C, MicroLogic 4.3 electronic trip unit, 100 kA Icu at 240 V AC, EN/IEC 60947-2.

$2,707.47 – $6,798.60Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C63H44V570 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C63H44V570 — Electrical Ratings
ParameterValue
Rated current (In)570 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C63H44V570 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX630H
C63H44V570 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C63H44V570 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C63H44V570 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C63H44V570 is a ComPacT NSX630H moulded-case circuit breaker, 4-pole, rated 570 A at 40 °C. It carries a MicroLogic 4.3 electronic trip unit that bundles overload (L), short-time short-circuit (So), instantaneous short-circuit (I), and integrated earth-leakage (R) protection into one package — that's four protection functions in one device, which simplifies panel wiring and saves a separate earth-leakage relay. Breaking capacity is 100 kA Icu at 240 V AC and 70 kA at 415 V AC per IEC 60947-2, with a 65 kA Icu at 480 V AC per UL 60947-4-1. That puts it in the H (high) breaking-capacity class — sized for main feeders in heavy industrial distribution where fault currents run high.

If your ambient in the enclosure runs higher, you derate — the trip unit is electronic, so the thermal memory holds the last 20 minutes of heating before and after a trip, which means it won't reclose into a still-hot load. IP40 front face, IK07 impact rating — fine for a clean indoor switchboard, not for washdown zones. That's the highest overvoltage category for a breaker — it handles the surges that hit the main incoming supply.

Frequently asked questions

What is the breaking capacity of C63H44V570 at 415 V?

70 kA Icu at 380/415 V AC per IEC 60947-2, which is the H-class rating for the NSX630H frame.

What protection functions does the MicroLogic 4.3 trip unit provide?

It covers overload (L) with long-time delay, short-time short-circuit (So) with fixed delay, instantaneous short-circuit (I), and integrated earth-leakage (R) — four functions in one electronic trip unit.

MPN