Schneider Electric C63H47E570 — Residual Current Breakers (RCCB/RCBO)

Schneider C63H47E570 ComPacT NSX MCCB, 570 A, 100 kA, 4-pole

MPNC63H47E570
Active

Schneider C63H47E570 Compact Nsx, New Generation — now discontinued, supplied from remaining surplus and broker stock.

$3,301.25Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

C63H47E570 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C63H47E570 — Electrical Ratings
ParameterValue
Rated current (In)570 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C63H47E570 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX630H
C63H47E570 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C63H47E570 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C63H47E570 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Overview

The C63H47E570 is a Schneider ComPacT NSX molded case circuit breaker with a MicroLogic 7.3 E electronic trip unit, rated 570 A at 40 °C and 100 kA ICU at 440 V AC. It carries L, S, I, and R protection curves for distribution duty.

Compared to the 3-pole C63N3 (630 A, 85 kA), the C63H47E570 adds a fourth pole and a higher 100 kA ICU, but its 570 A frame is slightly smaller. Pick the C63N3 when the BOM requires 3-pole and 630 A; the C63H47E570 suits 4-pole distribution with higher fault capacity.

MPN
C63H47E570