Skip to main content
Schneider Electric C63N37E570 — Residual Current Breakers (RCCB/RCBO)

Schneider C63N37E570 ComPacT NSX MCCB, 570 A, 85 kA, 3-pole

MPNC63N37E570
Active

Schneider C63N37E570 Compact Nsx, New Generation — now discontinued, supplied from remaining surplus and broker stock.

$2,748.96Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

C63N37E570 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C63N37E570 — Electrical Ratings
ParameterValue
Rated current (In)570 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C63N37E570 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX630N
C63N37E570 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C63N37E570 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C63N37E570 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Overview

The C63N37E570 is a Schneider ComPacT NSX molded case circuit breaker rated 570 A continuous at 40 °C, with an 85 kA interrupting capacity (ICu) at 440 V AC, 3-pole, and fitted with a MicroLogic 7.3 E electronic trip unit that provides L, S, I, and earth-leakage (R) protection curves.

The 85 kA ICu at 440 V AC gives this breaker headroom for high-fault installations; the 570 A frame and MicroLogic 7.3 E trip unit suit distribution feeders where earth-leakage detection is required alongside overload and short-circuit protection.

Compared to the C63H4, which is a 4-pole basic frame rated 630 A at 690 V AC, the C63N37E570 is a 3-pole earth-leakage breaker rated 570 A at 440 V AC — pick the C63H4 when the BOM requires 4 poles or a higher voltage rating, and the C63N37E570 when earth-leakage protection and a lower voltage distribution system are specified.

MPN
C63N37E570