Part identity and sourcing status
The CAD506FDS207: Rated operational voltage is 690 V, and it carries utilisation categories AC-15, DC-13, and AC-14 — meaning it's rated for switching solenoid loads, electromagnetic clutches, and contactor coils in control circuits.
The 5 NO contact arrangement gives you five independent normally-open circuits, all switching together. That's useful for distributing a single control signal to multiple loads — think contactor coils, pilot lights, or PLC inputs that need simultaneous closure. This relay lives inside an enclosure — it's not for washdown areas or outdoor panels without a cover. The TH protective treatment per IEC 60068 means it's been tested for tropical conditions — humidity and fungus resistance — so it's fine for non-condensing damp environments. Mechanical robustness specs: the relay stays closed under 15 Gn shock for 11 ms, open under 10 Gn. Vibration resistance is 4 Gn closed, 2 Gn open across 5-300 Hz. That's enough for most fixed industrial machinery; for high-vibration applications like mobile equipment, you'd want to check the mounting orientation.
Physical integration
Dimensions are 77 mm high, 45 mm wide, 93 mm deep.