It's rated for control-circuit duty up to 690 V and carries utilisation categories AC-15, AC-14, and DC-13 — so it handles solenoid and contactor coils, resistive loads, and moderate inductive DC loads on the same block.
Five NO contacts give you five independent switching channels — enough to interlock a small motor starter, feed multiple pilot lights, or control a safety circuit without stacking auxiliary blocks. The 32 V AC coil is a common control voltage in older European panels and some OEM machines; if your panel runs 24 V DC or 110 V AC, you'll need a different coil variant in the TeSys Deca family. The 93 mm depth and 45 mm width mean it fits a standard DIN-rail footprint without overhang into the wiring duct — important when you're retrofitting into a crowded enclosure. IP2X front-face protection (VDE 0106) means fingers won't reach live parts once it's mounted, so no extra shrouding needed on the panel door. Operating temperature from -40 to 60 °C (with derating up to 70 °C) covers most indoor and outdoor cabinet environments in temperate and cold climates. The TH protective treatment per IEC 60068 means it's built for humid, tropical conditions — no extra conformal coating required for shipping to coastal or high-humidity sites.