It uses a 48V DC low-consumption coil and terminates via snap-in terminals for quick panel wiring. Rated for utilisation categories AC-15, AC-14, and DC-13, this relay handles solenoid and electromagnetic loads typical in control panels — AC-15 covers electromagnetic devices above 72 VA, AC-14 covers those below 72 VA, and DC-13 covers solenoids with a DC coil. The 5NO contact arrangement gives you five independent normally-open switching paths in a single 45 mm wide package. The relay is approved to EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1, so it passes inspection for panels shipping to North America, Europe, China, and Japan.
The CAD50AEL measures 45 mm wide by 107 mm high by 93 mm deep — a standard TeSys Deca footprint that clips onto a DIN rail inside the control cabinet. The front face carries IP2X protection per VDE 0106, meaning finger-safe against accidental contact when the panel door is open. Operating temperature spans -40 to 60 °C, with derating allowed up to 70 °C. Storage range is -60 to 80 °C.
For BOM freeze or compliance audits, the relay carries protective treatment TH conforming to IEC 60068 (tropicalisation) and mechanical robustness ratings: shocks of 10 Gn for 11 ms (relay open) and 15 Gn for 11 ms (relay closed), plus vibration resistance of 2 Gn (open) and 4 Gn (closed) across 5-300 Hz per IEC 60068-2-27 and IEC 60068-2-6.