Breaking capacity is 4500 A at 230/400 V AC, 50/60 Hz, certified to IEC 60898-1.
The 6 A rating and C curve govern selectivity: downstream of a 16 A or 20 A C-curve MCB, this 6 A unit clears a fault before the upstream device trips, keeping the rest of the panel live. The 1P (single-pole) format protects one phase; neutral is switched separately or via a linked device.
Integration notes
Width is 18 mm (one module). Tunnel terminals accept 1…25 mm² rigid or 1…16 mm² flexible; tighten to 2 N·m. Strip length 14 mm. The grey housing carries a contact-position indicator and is compatible with comb busbars and distribution blocks.