Its 4.5 kA breaking capacity at 230/400 V AC per IEC 60898-1 is sized for residential and light commercial distribution boards where fault levels stay under that threshold.
The tunnel terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible copper, with a tightening torque of 2 N.m. The IP20 finger-safe enclosure suits enclosed distribution boards; not rated for wet or dusty environments.
This part is marked obsolete by the manufacturer. The paperwork has to be clean: the part carries IEC 60898-1 certification and SNI 04-6507.1, so compliance documentation for those standards is available on request.