Skip to main content
Schneider Electric DOMF01106 — 1-Pole MCB (DIN Rail)

Schneider Electric DOMF01106 Domae MCB, 1P, 6 A, C Curve, 6

MPNDOMF01106
Active

Schneider Electric Domae range, miniature circuit-breaker, 1P, 6 A, C curve, 6000 A breaking capacity, IEC 60898-1, DIN rail clip-on, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

DOMF01106 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product rangeDomae
Device short nameDomae MCB
Poles description1P
Number of protected poles1
Device applicationProtection
DOMF01106 — Electrical & Protection
ParameterValue
Rated current (In)6 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)Icn 6000 A
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
DOMF01106 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (top or bottom) - 1...25 mm² - rigid Tunnel type terminals (top or bottom) - 1...16 mm² - flexible
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth71.5 mm
Tightening torque (by circuit)2 N.m top or bottom
DOMF01106 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
DOMF01106 — Approvals
ParameterValue
Conformity standardsIEC 60898-1

Product details

The DOMF01106 is a single-pole Domae miniature circuit breaker rated 6 A with a C curve and 6000 A breaking capacity per IEC 60898-1. It clips onto a DIN rail — standard 18 mm width, 2 x 9 mm pitch — so it slots into any residential or light commercial distribution board without eating extra space. The thermal-magnetic trip unit clears overloads and short-circuits on a 230 V AC 50/60 Hz network.

The C curve means the magnetic trip fires at 5 to 10 times In (30 to 60 A). That's the standard choice for general-purpose loads — lighting, socket circuits, small appliances — where inrush isn't extreme but you still want selectivity against a short-circuit. Overvoltage category III (distribution level) means it's rated for permanent connection to the mains supply, not just a downstream device.

Frequently asked questions

What is the breaking capacity of DOMF01106?

The rated short-circuit breaking capacity (Icn) is 6000 A per IEC 60898-1 at 230 V AC.

What does the C curve mean on this breaker?

The magnetic trip threshold is 5 to 10 times the rated current (30 to 60 A for the 6 A version), which suits general-purpose loads like lighting and socket circuits.

Where can I buy DOMF01106 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

MPN
DOMF01106