It clips onto DIN rail for panel integration, occupying 2 x 9 mm pitches (18 mm wide).
The 32 A rating and C curve are the load-bearing specs. Single-pole (1P) protects one phase; no earth-leakage module inside, so if you need RCD protection, it goes downstream or as a combined device.
Clip-on mount to 35 mm DIN rail. Tunnel terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible copper; strip 14 mm, torque to 2 N·m. Comb busbar compatible for daisy-chaining multiple poles. IP20 finger-safe on the front face; IP40 inside a modular enclosure. Operating range -5 to 60 °C, storage -40 to 85 °C, with tropicalisation class 2 per IEC 60068-1 for damp-heat environments.