Skip to main content
Schneider Electric DOMF01150 — 1-Pole MCB (DIN Rail)

Schneider Electric DOMF01150 Domae MCB, 1P, 50 A, C Curve, 6

MPNDOMF01150
Active

Schneider Electric Domae, miniature circuit-breaker, 1P, 50 A, C Curve, 6000 A breaking capacity, IEC 60898-1, DIN rail clip-on, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

DOMF01150 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product rangeDomae
Device short nameDomae MCB
Poles description1P
Number of protected poles1
Device applicationProtection
DOMF01150 — Electrical & Protection
ParameterValue
Rated current (In)50 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)Icn 6000 A
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
DOMF01150 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (top or bottom) - 1...35 mm² - rigid Tunnel type terminals (top or bottom) - 1...25 mm² - flexible
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth71.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom
DOMF01150 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
DOMF01150 — Approvals
ParameterValue
Conformity standardsIEC 60898-1

Product details

The DOMF01150 is a single-pole Domae miniature circuit breaker rated 50 A with a C curve (magnetic trip between 5 and 10 times In) and an Icn of 6000 A per IEC 60898-1. The C curve means it handles moderate inrush — typical for lighting, socket circuits, and small motor loads in commercial or residential panels — without nuisance tripping. The 6000 A breaking capacity is the standard domestic/commercial level; if your installation's prospective short-circuit current exceeds that, you need a higher-rated device upstream for selectivity. Thermal-magnetic trip technology combines a bimetal strip for overload protection (time-delayed) and a solenoid for short-circuit protection (instantaneous).

Clip-on mounting to DIN rail, 18 mm width (2 x 9 mm pitches), 81 mm height, 71.5 mm depth — standard modular footprint that fits any 1P slot in a Domae or compatible distribution board. Tunnel terminals accept 1–35 mm² rigid or 1–25 mm² flexible cable; strip length 14 mm, tightening torque 3.5 N.m. Comb busbar compatible, so you can feed multiple MCBs from a single supply bar without daisy-chaining wire.

Frequently asked questions

What is the breaking capacity of DOMF01150?

The Icn (rated short-circuit breaking capacity) is 6000 A per IEC 60898-1.

MPN
DOMF01150