Schneider Electric DOMF01232 — 2-Pole MCB (DIN Rail)

Schneider Electric DOMF01232 Domae MCB, C Curve, 32 A, 2P

MPNDOMF01232
Active

Schneider Electric Domae series miniature circuit breaker, DOMF01232, 2-pole, C-curve, 32 A rated current, 6000 A breaking capacity, DIN-rail clip-on, IEC 60898-1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

DOMF01232 — Identification
ParameterValue
Series / familyDomae
Device short nameDomae MCB
Product / component typeMiniature circuit-breaker
Device applicationProtection
DOMF01232 — Electrical
ParameterValue
Rated current [In]32 A
Number of protected poles1
Pole configuration2P
Rated operational voltage [Ue]230 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
DOMF01232 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu)Icn 6000 A
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
DOMF01232 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth71.5 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals (top or bottom) - 1...25 mm² - rigid Tunnel type terminals (top or bottom) - 1...16 mm² - flexible
Terminal tightening torque2 N.m top or bottom
Comb busbar / distribution block compatibilityYES
DOMF01232 — Environmental
ParameterValue
Operating temperature range-5...60 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
DOMF01232 — Approvals
ParameterValue
Standards / complianceIEC 60898-1

Product details

The Schneider Electric DOMF01232 is a Domae-series miniature circuit breaker (MCB) with a C curve, rated 32 A, 2 poles, and an Icn of 6000 A per IEC 60898-1. The thermal-magnetic trip element handles overloads (the thermal bimetal) separately from short circuits (the solenoid), so you get time-delayed protection on sustained overcurrent and instant clearing on a hard fault. At 32 A and 2 poles, this is a double-pole MCB protecting both line conductors on a single-phase 230 V circuit, or one leg of a split-phase service.

Tunnel terminals accept 1–25 mm² rigid or 1–16 mm² flexible on top or bottom; strip length 14 mm, tighten to 2 N·m. The 18 mm phase-to-phase pitch means standard comb busbars fit without modification.

Frequently asked questions

What is the breaking capacity of DOMF01232?

Icn 6000 A per IEC 60898-1 at 230 V AC. That is the standard domestic and light-commercial rating — enough for most residential final circuits, but check your prospective short-circuit current (PSCC) at the panel if you are near a transformer or in a commercial riser.

What does the C curve mean on this MCB?

Magnetic trip operates between 5 and 10 times In — so for the 32 A DOMF01232, instantaneous trip occurs between 160 A and 320 A. This curve is chosen for loads with moderate inrush: small motors, fluorescent lighting banks, transformers, and general-purpose socket circuits where a B curve would trip on startup current.

Where can I buy DOMF01232 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here, but a procurement inquiry will return a firm price and lead time for the quantity you need.