Skip to main content
Schneider Electric E125H320FM — Circuit Breaker Accessories

Schneider Electric E125H320FM

MPNE125H320FM
Active

circuit breaker, EasyPact CVS, 1250A, 70kA, 3P3D, 415V AC

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

E125H320FM — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact CVS
Product rangeEasyPact
Device applicationLow voltage electrical distribution
E125H320FM — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]1250 A at 50 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz
Rated insulation voltage [Ui]800 V AC conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]8 kV conforming to IEC 60947-3
Network frequency50/60 Hz
Poles description3P
E125H320FM — Protection & Performance
ParameterValue
Breaking capacity80 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 60 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]80 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 60 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH 70 kA 415 V AC
Trip unit technologyElectronic
Trip unit rating1250 A at 50 °C
Trip unit nameETS 2.0
Protection typeL : for overload protection (long time) I : for instantaneous short-circuit protection
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Mechanical durability5000 cycles
Electrical durability3000 cycles at 415 V In 2000 cycles at 440 V In
Local signalling4 LEDs (red) for fault indication 1 LED (yellow) for overload
E125H320FM — Mechanical
ParameterValue
Connection pitch70 mm
Downside connectionFront
Upside connectionFront
Device short nameCVS1250H
Control typeRotary handle Toggle
Mounting modeFixed
Mounting supportBackplate
Width210 mm
Height327 mm
Depth147 mm
E125H320FM — Environmental
ParameterValue
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60664-1
Operating ambient air temperature-25...70 °C
Storage ambient air temperature-50...85 °C
E125H320FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
MPN
E125H320FM