Skip to main content
Schneider Electric EF548292 — Air Circuit Breakers

Schneider Electric EF548292

MPNEF548292
Active

switch-disconnector Masterpact P&P NW20HF - 2000 A - 690 V - 3 poles - drawout

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

EF548292 — Identification
ParameterValue
Product typeSwitch disconnector
Product nameMasterpact P&P NW20
RangeMasterPact
Product rangeMasterpact P&P NW
ApplicationDistribution
EF548292 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)2000 A AC 50/60 Hz 690 V
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3
EF548292 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85 kA during 1 s conforming to IEC 60947-3 75 kA during 3 s conforming to IEC 60947-3
Rated short-circuit making capacity (Icm)187 kA 220...690 V AC at 50/60 Hz
Breaking capacity codeHF
EF548292 — Performance
ParameterValue
Mechanical durability (cycles)10000 cycles without maintenance conforming to IEC 60947-3 20000 cycles with maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 6000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 8000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
EF548292 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Contact position indicatorYes
Width442 mm
Height352 mm
Depth297 mm
Connection pitch115 mm
EF548292 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-35...85 °C
Pollution degree4 conforming to IEC 60664-1
EF548292 — Approvals
ParameterValue
StandardsIEC 60947-3
MPN