Skip to main content
Schneider Electric ENW12701 — Air Circuit Breakers

Schneider Electric ENW12701 EasyPact NW Trip System 6.0s, LS

MPNENW12701
Active

Schneider Electric EasyPact NW, Trip System 6.0s control unit, LSIG protection, 630…6300 A, 690 V AC, 50/60 Hz, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ENW12701 — Identification
ParameterValue
Product typeControl unit
Product rangeEasyPact NW
ENW12701 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P 3P
Network typeAC
Network frequency50/60 Hz
ENW12701 — Mechanical & connection
ParameterValue
Mounting modeFixed
Width58 mm
Height200 mm
Depth77 mm
Neutral pole positionLeft
ENW12701 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C

Product details

The Schneider Electric ENW12701 is a Trip System 6.0s control unit for the EasyPact NW range of air circuit breakers. It provides LSIG protection — overload (long-time), short-time short-circuit, instantaneous short-circuit, and earth fault — via a microprocessor-based trip unit rated 630…6300 A. That means it coordinates with the breaker's interrupting capacity under fault conditions up to that voltage.

Protection and adjustment detail

Long-time pick-up (Ir) adjusts from 0.4 to 1 x In in 10 steps, with a delay (Tr) from 0.5 to 24 s at 6 x Ir (accuracy 0 to -20 %). Short-time pick-up (Isd) also offers 10 settings, delay (Tsd) from 100 to 600 ms. Instantaneous pick-up (Ii) covers 2 to 15 x In, accuracy ±10 %, also adjustable in 10 steps. Ground-fault pick-up has 10 settings. Thermal memory is included, so the trip unit accounts for prior heating when re-energizing after a trip — critical for motor and transformer feeders where repeated overloads degrade insulation faster than a single event.

Physical integration and connectivity

Dimensions: 200 mm high, 58 mm wide, 77 mm deep. Fixed mounting mode. The neutral position is left; pole configurations available are 4P and 3P, with protected poles configurable as 3D, 3D + N/2, or 4D. Neutral protection can be set to without protection (3D), 0.5 x Ir (3D + N/2), or 1 x Ir (4D). Communication via NFC wireless peer-to-peer and USB Type-C interface. Status is indicated by a green, red, and orange health status bar plus a green ready LED. Fault indication covers short-circuit, overload, earth fault, and internal fault. Control button is a single I button with LED indication. Data recording includes alarm logs, event logs, and trip logs — useful for post-event analysis without needing external software. Battery type is lithium non-rechargeable, which powers the trip unit's memory and clock during de-energized periods.

This control unit is designed for industrial standard circuit breaker applications. It is a component of the EasyPact NW family, which covers air breakers from 630 A up to 6300 A.

Frequently asked questions

What are the key protection functions of ENW12701?

The ENW12701 Trip System 6.0s provides LSIG protection: overload (long-time), short-time short-circuit, instantaneous short-circuit, and earth fault. It is microprocessor-based with fully adjustable settings.

What is the voltage and standard rating for ENW12701?

Rated operational voltage is 690 V AC at 50/60 Hz, conforming to IEC 60947-2.

Where can I buy ENW12701?

The ENW12701 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN