Schneider Electric ENW12702 — Air Circuit Breakers

Schneider Electric ENW12702 EasyPact NW Trip Unit, LSIG, 630

MPNENW12702
Active

Schneider Electric EasyPact NW, Trip System 6.0s microprocessor-based control unit, LSIG protection, 630–6300 A, 690 V AC IEC 60947-2, drawout mount, 77 x 58 x 200 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ENW12702 — Identification
ParameterValue
Product typeControl unit
Product rangeEasyPact NW
ENW12702 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P 3P
Network typeAC
Network frequency50/60 Hz
ENW12702 — Mechanical & connection
ParameterValue
Mounting modeDrawout for frame 1
Width58 mm
Height200 mm
Depth77 mm
Neutral pole positionLeft
ENW12702 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C

Product details

What this trip unit does

The ENW12702 is a microprocessor-based control unit for the Schneider Electric EasyPact NW range of air circuit breakers. It provides LSIG protection — overload (long-time), short-time short-circuit, instantaneous short-circuit, and earth fault — adjustable across ten settings per function. The trip unit rating spans 630 to 6300 A, and it operates at 690 V AC 50/60 Hz, certified to IEC 60947-2. That means it can be dialled in for everything from a 630 A feeder to a 6300 A main, with selectivity coordination possible across the full band.

Drawout mount for frame 1 — pulls out without unbolting busbars, which is the kind of detail a field-service tech appreciates when the line is down and every minute counts. Dimensions are 77 mm deep, 58 mm wide, 200 mm tall, fitting the standard EasyPact NW cradle. Neutral position is left; poles configurable as 3P or 4P with neutral protection settings (3D, 3D+N/2, 4D).

Adjustments and diagnostics

Long-time pickup (Ir) adjustable 0.4–1 x In with ten settings; short-time pickup (Isd) also ten settings; instantaneous (Ii) adjustable 2–15 x In, also ten settings. Ground-fault pickup has its own ten settings. The long-time delay (Tr) spans 0.5–24 s at 6 x Ir with 0 to –20% accuracy; short-time delay (Tsd) is 100–600 ms. Thermal memory is included, so the unit remembers prior heating — essential for motor feeders or repeated reclosure scenarios. Data recording covers alarm, event, and trip logs, and the status LED shows green, red, and orange health bars plus a green ready indicator. Fault indication flags short-circuit, overload, earth fault, and internal fault.

Communications and power

Onboard NFC and USB Type-C for peer-to-peer wireless interface — no special dongle needed; a smartphone app can pull trip logs or adjust settings. Battery is lithium non-rechargeable, which backs the clock and event logs during a power loss. Network type is AC, 50/60 Hz.

Frequently asked questions

What protection functions does the ENW12702 provide?

It provides LSIG protection: overload (long-time), short-time short-circuit, instantaneous short-circuit, and earth fault, all with multiple adjustable settings.

What is the trip unit rating range for ENW12702?

The trip unit rating is 630 to 6300 A, adjustable via ten settings per protection function.

How is the ENW12702 mounted?

It uses a drawout mount for frame 1, allowing removal without disturbing busbars. Dimensions are 77 mm deep, 58 mm wide, 200 mm tall.

What communications interfaces does the ENW12702 have?

It has NFC and USB Type-C for peer-to-peer wireless interface, plus a lithium battery for backing logs during power loss.

Where can I buy ENW12702 and how is it quoted?

The ENW12702 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
ENW12702