Skip to main content
Schneider Electric ENW13201 — Air Circuit Breakers

Schneider Electric ENW13201 EasyPact NW Circuit Breaker, 630

MPNENW13201
Active

Schneider Electric EasyPact NW ENW13201, 3P drawout circuit breaker, 630 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ENW13201 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW13201 — Electrical ratings
ParameterValue
Rated current (In)630 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
ENW13201 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeC
ENW13201 — Performance
ParameterValue
Breaking time, max.35 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
ENW13201 — Mechanical & connection
ParameterValue
Mounting modeDrawout
Mounting supportRail Base plate
Contact position indicatorYes
Width288 mm
Height322 mm
Depth277 mm
Connection pitch70 mm without spreader
Connection locationRear
ENW13201 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to IEC 60664-1
ENW13201 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

Schneider Electric ENW13201 is a 3-pole drawout circuit breaker from the EasyPact NW family, rated 630 A at 40 °C with a breaking capacity of 66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2.

Drawout mounting and panel integration

Mounts on a rail base plate with drawout mechanism — the breaker can be racked out for maintenance or replacement without disturbing the main bus connections. Rear connection terminals accept horizontal or vertical bus bars; connection pitch is 70 mm without a spreader. Overall dimensions are 288 mm wide × 322 mm high × 277 mm deep, so plan for a cutout that accommodates the drawout cradle plus clearance for arc chute venting.

Rated for 20,000 mechanical cycles with maintenance (10,000 without) and 5,000 electrical cycles at 440 V AC without maintenance — this is a Category B breaker, meaning it's designed for selective coordination with downstream devices.

Frequently asked questions

Where can I buy ENW13201 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is ENW13201's breaking capacity at 440 V?

66 kA Icu (ultimate breaking capacity) and 55 kA Ics (service breaking capacity) at 220...440 V AC 50/60 Hz per IEC 60947-2.

What standards does ENW13201 comply with?

IEC 60947-2 for circuit breakers, with isolation suitability confirmed per that standard. Pollution degree 3 per IEC 60664-1.

MPN