Skip to main content
Schneider Electric ENW13205

Schneider Electric ENW13205 EasyPact NW Circuit Breaker, 160

MPN ENW13205
Active

Schneider Electric EasyPact NW, drawout circuit breaker, ENW16C, 1600 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2, 3P.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW13205 key specifications
ParameterValue
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP30
Terminal pitch70 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-40...85 °C

All specifications

ENW13205 additional specifications
ParameterValue
Pollution degreeclass 3
Depth277 mm
Width288 mm
Height322 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...70 °C

Product details

What the 1600 A and 66 kA ratings mean for fit

The Schneider Electric ENW13205 is an EasyPact NW drawout circuit breaker rated 1600 A at 40 °C with a breaking capacity of 66 kA Icu at 220…440 V AC 50/60 Hz per IEC 60947-2. The rated short-time withstand current Icw is 50 kA for 1 s, which matters for selective coordination downstream — the breaker holds in during a fault long enough for an upstream device to clear. This is a 3-pole, Category B breaker, meaning it's intended for distribution duty with full selectivity capability — not just cable protection. The 1000 V rated insulation voltage and 12 kV impulse withstand confirm it's built for industrial switchgear environments, not light commercial panels. Drawout mounting on a rail base plate means the breaker can be racked out for maintenance without disturbing the bus connections — a standard requirement for main or tie breakers in a switchgear lineup.

Mounts on a rail base plate in drawout configuration — the breaker unit slides in and out, leaving the base and power connections fixed. Connection pitch is 70 mm without spreader; rear connections are standard for switchgear bus risers.

MPN