Skip to main content
Schneider Electric ENW13218 — Air Circuit Breakers

Schneider Electric ENW13218 EasyPact NW Circuit Breaker, 800

MPNENW13218
Active

Schneider Electric EasyPact NW, circuit breaker, ENW13218, 800 A at 40 °C, 4 poles, 66 kA Icu at 440 V AC, drawout mounting, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ENW13218 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW13218 — Electrical ratings
ParameterValue
Rated current (In)800 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
ENW13218 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeC
ENW13218 — Performance
ParameterValue
Breaking time, max.35 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
ENW13218 — Mechanical & connection
ParameterValue
Mounting modeDrawout
Mounting supportRail Base plate
Contact position indicatorYes
Width358 mm
Height322 mm
Depth277 mm
Neutral pole positionLeft
Connection pitch70 mm without spreader
Connection locationRear
ENW13218 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to IEC 60664-1
ENW13218 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

What the 800 A and 66 kA Icu ratings mean for your switchgear lineup

The Schneider Electric ENW13218 is an EasyPact NW drawout circuit breaker rated 800 A at 40 °C, with a 66 kA Icu breaking capacity at 220–440 V AC 50/60 Hz per IEC 60947-2. For repeated fault clearing, the Ics (service breaking capacity) is 55 kA at the same voltage range, which is the level it can handle and still carry rated current afterward. Both ratings govern the fault-withstand coordination study for your distribution board. The drawout mounting means the breaker chassis stays bolted to the rail base plate while the moving portion slides out for inspection or swap — no need to disconnect main power cables for routine maintenance. The 4-pole configuration with neutral on the left suits three-phase plus neutral distribution panels common in industrial and commercial switchgear.

Integration into a panel or switchgear lineup

Mounts on a rail base plate with a 70 mm connection pitch without spreader. The rear connection location and horizontal/vertical connection orientation give flexibility in busbar or cable routing. At 358 mm wide × 322 mm high × 277 mm deep, it fits standard low-voltage switchgear compartments — verify the cutout and door clearance for the drawout racking mechanism.

Designed and tested to IEC 60947-2 for low-voltage switchgear and controlgear. Rated insulation voltage 1000 V AC, rated impulse withstand voltage 12 kV, and suitability for isolation — all per that standard. The IP30 degree of protection is typical for enclosed switchgear; the enclosure itself provides the higher IP rating. Ambient operating range -5 to 70 °C covers most indoor installations; storage range -40 to 85 °C covers shipping and warehousing.

Frequently asked questions

Where can I buy the ENW13218 and what is the lead time?

The ENW13218 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the specific quantity and delivery window.

What is the breaking capacity of the ENW13218?

The ultimate breaking capacity (Icu) is 66 kA at 220–440 V AC 50/60 Hz per IEC 60947-2. The service breaking capacity (Ics) is 55 kA at the same voltage. The rated short-time withstand current (Icw) is 50 kA for 1 second.

What standards does the ENW13218 comply with?

It complies with IEC 60947-2 for low-voltage switchgear and controlgear, with a rated insulation voltage of 1000 V AC and rated impulse withstand voltage of 12 kV. It is suitable for isolation per that standard.

MPN