Skip to main content
Schneider Electric ENW13220

Schneider Electric ENW13220 EasyPact NW Circuit Breaker, 125

MPN ENW13220
Active

Schneider Electric EasyPact NW, circuit breaker, ENW13220, 4P, 1250 A at 40 °C, 66 kA Icu at 440 V AC, drawout mounting, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW13220 key specifications
ParameterValue
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP30
Terminal pitch70 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-40...85 °C

All specifications

ENW13220 additional specifications
ParameterValue
Pollution degreeclass 3
Depth277 mm
Width358 mm
Height322 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW13220 is a 4-pole EasyPact NW drawout circuit breaker rated 1250 A at 40 °C, built for distribution duty per IEC 60947-2. The 55 kA Ics service rating tells you it can reclose after a fault at that level without maintenance, which matters on a continuous process line where a nuisance trip can't turn into a shift-long outage.

Drawout mounting and panel integration

Drawout mounting means the breaker chassis stays wired to the bus; the moving portion slides out for inspection or swap without disturbing the rear connections. The 70 mm connection pitch without spreader and rear horizontal/vertical connection positions give the panel builder options for busbar routing. Mounts on a rail base plate. IP30 is standard for enclosed switchgear — not for open panel fronts, but fine behind a door.

The 1250 A frame is the continuous current at 40 °C — size your bus and lugs for that, not less. The 66 kA Icu is the ultimate breaking capacity; the 55 kA Ics is the service rating after a fault. The 50 kA Icw for 1 second is the short-time withstand — critical for selective coordination downstream.

MPN
ENW13220