Specifications

ENW13226 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW13226 — Electrical ratings
ParameterValue
Rated current (In)800 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
ENW13226 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeC
ENW13226 — Performance
ParameterValue
Breaking time, max.35 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
ENW13226 — Mechanical & connection
ParameterValue
Mounting modeFixed
Mounting supportRail Base plate
Contact position indicatorYes
Width346 mm
Height301 mm
Depth196 mm
Neutral pole positionLeft
Connection pitch70 mm without spreader
Connection locationRear
ENW13226 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to IEC 60664-1
ENW13226 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW13226 is an EasyPact NW fixed-mount circuit breaker rated for 800 A at 40 °C, with a 66 kA Icu breaking capacity at 220...440 V AC 50/60 Hz per IEC 60947-2. It's a 4-pole unit (4P 3d protected poles) built for distribution duty in switchboards and industrial panels.

Both are verified at 440 V AC, the common industrial distribution voltage. The 50 kA Icw for 1 second tells you it can withstand a delayed trip from a downstream device, so you can build a selective cascade without worrying about the main blowing first.

Integration into the switchboard

This breaker mounts fixed to a rail base plate, rear-connected, with a 70 mm connection pitch without spreader. At 346 mm wide, 301 mm high, and 196 mm deep, it fits standard low-voltage switchgear cubicles. The neutral sits on the left. IP30 protection is basic finger-probe protection on the front; the real sealing happens in the enclosure.

Frequently asked questions

Where can I buy ENW13226 and how do I get a price?

The ENW13226 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is ENW13226's breaking capacity at 440 V?

The ENW13226 has a 66 kA Icu (ultimate breaking capacity) and a 55 kA Ics (service breaking capacity) at 220...440 V AC 50/60 Hz per IEC 60947-2.

What standards does the ENW13226 comply with?

The ENW13226 complies with IEC 60947-2 for circuit breakers, with a rated insulation voltage of 1000 V AC, impulse withstand voltage of 12 kV, and pollution degree 3 per IEC 60664-1.

What is the mechanical durability of the ENW13226?

The ENW13226 is rated for 20,000 cycles with maintenance and 10,000 cycles without maintenance, per IEC 60947-2.

MPN
ENW13226