ENW13227 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW13227 — Electrical ratings
ParameterValue
Rated current (In)1000 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
ENW13227 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeC
ENW13227 — Performance
ParameterValue
Breaking time, max.35 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
ENW13227 — Mechanical & connection
ParameterValue
Mounting modeFixed
Mounting supportRail Base plate
Contact position indicatorYes
Width346 mm
Height301 mm
Depth196 mm
Neutral pole positionLeft
Connection pitch70 mm without spreader
Connection locationRear
ENW13227 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to IEC 60664-1
ENW13227 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The ENW13227 is a 4P EasyPact NW circuit breaker from Schneider Electric, rated 1000 A at 40 °C and built to IEC 60947-2. The 66 kA Icu at 220...440 V AC 50/60 Hz is the maximum short-circuit current it can safely interrupt once — that's the ultimate breaking capacity, and it's the number that governs fault-clearing at the main distribution point. The 55 kA Ics (service breaking capacity) tells you it can clear that level repeatedly without needing replacement, which matters for a main breaker where faults are rare but the breaker stays in service. The 50 kA Icw for 1 second is the short-time withstand rating — the breaker can hold that current closed for a full second while downstream devices clear a fault, which is the coordination window you design selective tripping around. Rated insulation voltage is 1000 V AC, impulse withstand 12 kV — that's the clearance and creepage design for a 440 V operational voltage, giving a solid safety margin on a 400 V distribution bus. The IP30 enclosure keeps hands and tools out but expects panel-side protection from liquid ingress. Mechanical durability is 20000 cycles with maintenance, 10000 without — that's a lifetime figure for a fixed-mount distribution breaker that sees infrequent switching. Electrical durability is 5000 cycles at 440 V without maintenance, Category B, which aligns with its role as a distribution breaker rather than a motor-switching device.

Fixed mounting on a rail base plate, rear-connected. The 346 mm width by 301 mm height by 196 mm depth footprint fits standard low-voltage switchgear cubicles; the 70 mm connection pitch without spreader matches common busbar drilling patterns. Neutral on the left, connection positions both horizontal and vertical — gives flexibility in busbar routing.

Frequently asked questions

What are the key ratings for ENW13227?

Rated current 1000 A at 40 °C, breaking capacity 66 kA Icu at 220...440 V AC, service breaking capacity 55 kA Ics, short-time withstand 50 kA for 1 second, rated insulation voltage 1000 V AC, impulse withstand 12 kV.

Where can I buy ENW13227?

This part is sourced and quoted to order against an RFQ through independent distribution channels, with availability and current pricing confirmed at quote time.

What standard does ENW13227 comply with?

It complies with IEC 60947-2 for circuit breakers, with pollution degree 3 per IEC 60664-1 and suitability for isolation per IEC 60947-2.