Skip to main content
Schneider Electric ENW13228 — Air Circuit Breakers

Schneider Electric ENW13228 EasyPact NW Circuit Breaker, 125

MPNENW13228
Active

Schneider Electric EasyPact NW, circuit breaker, ENW13228, 1250 A, 66 kA Icu at 220-440 V AC, 4P, fixed mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

ENW13228 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW13228 — Electrical ratings
ParameterValue
Rated current (In)1250 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
ENW13228 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeC
ENW13228 — Performance
ParameterValue
Breaking time, max.35 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
ENW13228 — Mechanical & connection
ParameterValue
Mounting modeFixed
Mounting supportRail Base plate
Contact position indicatorYes
Width346 mm
Height301 mm
Depth196 mm
Neutral pole positionLeft
Connection pitch70 mm without spreader
Connection locationRear
ENW13228 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30
Pollution degree3 conforming to IEC 60664-1
ENW13228 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW13228 is a 4-pole EasyPact NW air circuit breaker rated 1250 A at 40 °C, built for distribution duty in AC networks at 50/60 Hz. The 55 kA Ics service breaking capacity tells you it can reclose after a fault at that level and still carry rated load, not just survive one shot.

Rated insulation voltage (Ui) of 1000 V AC and impulse withstand (Uimp) of 12 kV per IEC 60947-2. The 50 kA Icw for 1 second supports selective coordination studies. Mechanical durability of 20,000 cycles with maintenance and 10,000 without, plus electrical endurance of 5,000 cycles at 440 V without maintenance, puts this in the heavy-industrial bracket — not a daily-switch application, but fine for infrequent load-break or isolation duty.

Frequently asked questions

What is the breaking capacity of ENW13228?

The ENW13228 has a rated ultimate breaking capacity (Icu) of 66 kA at 220-440 V AC 50/60 Hz per IEC 60947-2, and a service breaking capacity (Ics) of 55 kA at the same voltage.

What compliance documentation does Schneider provide for ENW13228?

The breaker is certified to IEC 60947-2, with a rated insulation voltage of 1000 V AC and impulse withstand of 12 kV. It is suitable for isolation per the same standard. Specific RoHS/REACH/UL documentation should be requested at quote time.

MPN
ENW13228