Skip to main content
Schneider Electric ENW13269

ENW13269 EasyPact NW Switch Disconnector, 1600 A, 3P

MPN ENW13269
Active

Schneider Electric EasyPact NW, switch disconnector, ENW13269, 3 poles, 1600 A AC-23A, drawout, 1000 V insulation, 50 kA Icw.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW13269 key specifications
ParameterValue
Main product or component typeSwitch disconnector
Voltage440 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 1600 A AC 50/60 Hz 440 V
Utilization categoryAC-23 A
IP ratingIP30
Terminal pitch70 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-40...85 °C

All specifications

ENW13269 additional specifications
ParameterValue
Pollution degreeclass 3
Depth277 mm
Width288 mm
Height322 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The ENW13269 is a 3-pole switch disconnector from the Schneider Electric EasyPact NW range, rated 1600 A in AC-23A utilization category at 440 V AC — that's the heavy motor-switching duty class, so it handles the high inrush of starting motors and other inductive loads without welding contacts. It's a drawout unit, meaning the switching element slides out of its cradle for safe inspection or replacement without disturbing the main bus connections — a real time-saver in switchgear where uptime matters. Rated insulation voltage is 1000 V AC, with an impulse withstand of 12 kV and a short-time withstand of 50 kA for 1 second, so it's built for distribution panels where fault levels are substantial. It's certified as suitable for isolation per IEC 60947-3, meaning you can safely use it as a visible-break disconnecting means for lockout/tagout procedures.

Mounts on a rail base plate in drawout configuration — the 70 mm connection pitch without spreader matches standard busbar centers, and the rear connection location keeps cabling clean in a fixed-cradle setup. Dimensions are 322 mm high, 288 mm wide, 277 mm deep — factor that depth into your enclosure clearance, especially with the drawout rail travel.

MPN