Schneider Electric EasyPact NW, switch disconnector, ENW13284, 800 A, 3-pole, fixed mounting, AC-23A, 440 V.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW13284 key specifications
ParameterValue
Main product or component typeSwitch disconnector
Voltage440 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 800 A AC 50/60 Hz 440 V
Utilization categoryAC-23 A
IP ratingIP30
Terminal pitch70 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-40...85 °C without control unit

All specifications

ENW13284 additional specifications
ParameterValue
Pollution degreeclass 3
Depth196 mm
Width346 mm
Height301 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

What the 800 A AC-23A rating means for your distribution board

The Schneider Electric ENW13284 is a 3-pole switch disconnector from the EasyPact NW range, rated 800 A in AC-23A utilisation category at 440 V AC. The 12 kV impulse rating means it can survive transient overvoltages common in industrial distribution without flashover — relevant if your panel feeds long cable runs or sits near VFDs that generate switching spikes. Short-time withstand current (Icw) is 50 kA for 1 second at 220–440 V, and the rated short-circuit making capacity (Icm) is 75 kA at the same voltage range. For selectivity coordination, the 50 kA Icw tells you this switch can hold in during a downstream fault long enough for the upstream breaker to clear — it won't weld or blow open on a through-fault within that window.

Mounts fixed to a rail base plate — not a standard DIN rail, but a dedicated backplate that bolts into the enclosure. Dimensions are 346 mm wide by 301 mm high by 196 mm deep, so plan for a cabinet depth of at least 250 mm to allow rear cable access and bending radius. Connection is rear-entry only, vertical or horizontal orientation, with a 70 mm phase-to-phase pitch without spreader. That pitch matches standard busbar systems in 800 A switchgear — no adapter needed if your distribution uses 70 mm centres. IP30 protection means it's not sealed against water ingress — suitable for indoor switchboards only, not washdown or outdoor locations.

MPN