Skip to main content
Schneider Electric ENW21429 — Air Circuit Breakers

Schneider Electric ENW21429 EasyPact NW Control Unit, Trip S

MPNENW21429
Active

Schneider Electric EasyPact NW, control unit, Trip System 6.0E, LSIG protection, 800-4000 A, 690 V AC, microprocessor-based, current production.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

ENW21429 — Identification
ParameterValue
Product typeControl unit
Product rangeEasyPact NW
ENW21429 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P 3P
Network typeAC
Network frequency50/60 Hz
ENW21429 — Mechanical & connection
ParameterValue
Mounting modeFixed
Width55 mm
Height200 mm
Depth75 mm
Neutral pole positionLeft
ENW21429 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-25...85 °C

Product details

EasyPact NW control unit with Trip System 6.0E

The Schneider Electric ENW21429 is a microprocessor-based control unit for the EasyPact NW range of air circuit breakers, fitted with a Trip System 6.0E. It provides LSIG protection — overload (long-time), short-circuit (short-time and instantaneous), and earth-fault — across a trip unit rating of 800 to 4000 A, at a rated operational voltage of 690 V AC 50/60 Hz conforming to IEC 60947-2. The LSIG protection suite means this unit handles the full selectivity stack for industrial distribution: long-time pickup adjustable 0.4 to 1 x In across 9 settings, short-time pickup 1.5 to 10 x Ir (9 settings), instantaneous pickup 2 to 15 x In (9 settings, plus Off), and ground-fault pickup 0.2 to 1 x In for frames up to 1000 A, or 500 to 1200 x In above that. Zone selective interlocking (ZSI) is built in, so multiple breakers in a cascade can communicate fault direction and trim trip delays — critical for maintaining uptime on a switchboard bus. The digital display shows fault type (overload, earth fault, short-circuit, internal fault) and energy metering data — useful for power-quality logging without an extra panel meter.

Physical integration and wiring

Network frequency is 50/60 Hz. The long-time delay adjustment range is 0.5 to 24 seconds at 6 x Ir (accuracy 0 to -20%), short-time delay 100 to 400 ms.

Frequently asked questions

Where can I buy ENW21429 and how do I get a price?

ENW21429 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What protection functions does the Trip System 6.0E provide?

The Trip System 6.0E provides LSIG protection: overload (long-time), short-circuit (short-time and instantaneous), and earth-fault, with adjustable pickup and delay settings.

What is the rated voltage and current range for ENW21429?

Rated operational voltage is 690 V AC 50/60 Hz per IEC 60947-2; the trip unit rating is 800 to 4000 A.

MPN
ENW21429