Skip to main content
Schneider Electric ENW24105

Schneider Electric ENW24105 EasyPact NW Circuit Breaker, 200

MPN ENW24105
Active

Schneider Electric EasyPact NW air circuit breaker, ENW24105, 2000 A rated current, 50 kA Icu at 440 V AC, 3-pole drawout, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24105 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24105 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric ENW24105 is an EasyPact NW air circuit breaker rated 2000 A at 40 °C, with a breaking capacity of 50 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. The 42 kA Icu at 690 V AC tells you the same breaker handles higher-voltage distribution but with reduced fault-clearing margin. Drawout mounting means the breaker chassis slides into a fixed cradle, so you can rack it out for maintenance without disturbing the bus connections — standard for switchgear where uptime matters.

Deployment context

This breaker is designed for drawout mounting on a rail, typical in low-voltage switchgear lineups where the breaker must be removable for service without de-energizing the bus. IP40 protection means it is suited for indoor electrical rooms — not washdown environments. The rear connection position with a 115 mm pitch without spreader matches standard bus-bar takeoffs in switchgear cubicles.

Certified to IEC 60947-2 for low-voltage switchgear and controlgear. Pollution degree 4 per IEC 60664-1 — the highest severity, meaning it withstands conductive pollution (e.g., dust, moisture) in industrial environments. Rated insulation voltage 1000 V AC, impulse withstand 12 kV.

MPN
ENW24105