Skip to main content
Schneider Electric ENW24106 — Air Circuit Breakers

Schneider Electric ENW24106 EasyPact NW Circuit Breaker, 250

MPNENW24106
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24106, 3P, 2500 A at 40 °C, 50 kA Icu at 440 V AC, drawout mounting.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24106 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24106 — Electrical ratings
ParameterValue
Rated current (In)2500 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24106 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24106 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24106 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width441 mm
Height439 mm
Depth395 mm
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24106 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24106 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The ENW24106 is a 3-pole EasyPact NW circuit breaker rated 2500 A at 40 °C, with a breaking capacity of 50 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2. At 690 V the Icu drops to 42 kA, still sufficient for most industrial secondary distribution. The drawout mounting means the breaker chassis slides into a fixed cradle, allowing safe isolation and replacement without unbolting busbars — standard for switchgear lineups where maintenance access matters. Rated insulation voltage (Ui) is 1000 V AC, and the impulse withstand (Uimp) is 12 kV, confirming the part is designed for systems where transient overvoltages are a concern — typical in industrial environments with motor starts and capacitor switching.

Deployment context

This breaker is a drawout unit designed for mounting on a rail in low-voltage switchgear assemblies. The rear connection position with a 115 mm pitch without spreader matches standard busbar take-off spacing in common switchgear cubicles.

Key approvals and standards

Certified to IEC 60947-2 for low-voltage switchgear and controlgear. Suitability for isolation means it can be used as a disconnecting means per code. Electrical durability is 5000 cycles at 440 V and 2500 cycles at 690 V without maintenance; mechanical durability is 20000 cycles with maintenance, 10000 without. These figures guide preventive maintenance scheduling — plan inspection at the 5000-cycle mark for typical 440 V distribution.

Frequently asked questions

How do I get current pricing and availability for ENW24106?

Pricing and availability are confirmed at quote time. Submit an RFQ through this listing; the part is sourced to order through independent distribution.

What is ENW24106's rated breaking capacity?

The ENW24106 has a breaking capacity of 50 kA Icu at 220…440 V AC 50/60 Hz and 42 kA Icu at 690 V AC 50/60 Hz, both conforming to IEC 60947-2.

What is the rated current of ENW24106?

The rated current (In) is 2500 A at 40 °C.

MPN