Schneider Electric ENW24108

Schneider Electric ENW24108 EasyPact NW Circuit Breaker, 400

MPN ENW24108
Active

Schneider Electric EasyPact NW, air circuit breaker, ENW24108, 4000 A rated current, 55 kA Icu at 440 V AC, 3P, drawout mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24108 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
ApplicationDistribution
Operating temperature-5...60 °C

Product details

Rating and application context

The Schneider Electric ENW24108 is a 3-pole air circuit breaker from the EasyPact NW range, rated 4000 A at 40 °C with a breaking capacity of 55 kA Icu at 220...440 V AC and 42 kA Icu at 690 V AC, per IEC 60947-2. The drawout mounting allows the breaker to be racked out for maintenance or replacement without disturbing the bus connections, a standard requirement for switchgear lineups where uptime matters.

Withstand and coordination

The short-time withstand current (Icw) is 55 kA for 1 s at 220...440 V and 42 kA for 1 s at 690 V, with a 3 s rating of 30 kA at 440/690 V. This Icw value is the one you size selective coordination against — if the downstream breaker clears a fault within 1 s, this breaker must hold closed without damage.

Integration notes

Drawout mounting with rear connections — the breaker slides into a fixed cradle with horizontal or vertical connection orientation. The 115 mm connection pitch without spreader matches standard switchgear bus spacing.

Rated insulation voltage 1000 V AC, operational voltage 690 V AC. Electrical durability is 5000 cycles at 440 V and 2500 cycles at 690 V without maintenance; mechanical durability 20000 cycles with maintenance, 10000 without.