Skip to main content
Schneider Electric ENW24113 — Air Circuit Breakers

Schneider Electric ENW24113 EasyPact NW Circuit Breaker, 200

MPNENW24113
Active

Schneider Electric EasyPact NW, ENW24113, 3P circuit breaker, 2000 A at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, fixed mounting, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24113 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24113 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24113 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24113 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24113 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24113 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24113 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

It carries a 50 kA Icu breaking capacity at 220...440 V AC and 42 kA at 690 V AC, both per IEC 60947-2. The breaker is Category B (selective) per IEC 60947-2, so it coordinates with downstream devices: a short-time withstand rating of 50 kA for 1 second at 440 V lets it ride through a fault long enough for a branch breaker to clear, keeping the main bus live. The 12 kV impulse withstand voltage (Uimp) confirms it handles surge events common in industrial power systems.

Fixed-mount design on a base plate — no draw-out cradle. Rear connections with a 115 mm pitch (without spreader) for vertical or horizontal busbar orientation. Dimensions: 422 mm wide × 352 mm high × 297 mm deep. IP40 protection — tool-accessible openings only; no washdown rating. The push-button control on the front cover gives local open/close/reset without opening the door.

Frequently asked questions

Where can I buy the ENW24113 and what is the lead time?

The ENW24113 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time and price quote.

What is the breaking capacity of the ENW24113?

The ENW24113 has a rated ultimate breaking capacity (Icu) of 50 kA at 220...440 V AC and 42 kA at 690 V AC, both per IEC 60947-2. The service breaking capacity (Ics) is the same 50 kA / 42 kA respectively, meaning the breaker can be reclosed after a fault at those levels without derating.

What standards does the ENW24113 comply with?

The ENW24113 is designed and tested to IEC 60947-2 for low-voltage switchgear and controlgear. It is suitable for isolation per that standard, carries a pollution degree 4 rating per IEC 60664-1, and has a 12 kV impulse withstand voltage (Uimp).

MPN