Skip to main content
Schneider Electric ENW24116 — Air Circuit Breakers

Schneider Electric ENW24116 EasyPact NW Circuit Breaker, 400

MPNENW24116
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24116, 4000 A at 40 °C, 55 kA Icu at 440 V AC, 3P, IEC 60947-2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24116 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24116 — Electrical ratings
ParameterValue
Rated current (In)4000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24116 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 55 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2 121 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity55 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24116 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24116 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24116 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24116 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24116 is an EasyPact NW air circuit breaker rated 4000 A at 40 °C, with a 55 kA Icu breaking capacity at 220…440 V AC 50/60 Hz per IEC 60947-2. Three-pole (3P), fixed-mount on a base plate, with rear vertical or horizontal connection. IP40 protection makes it suitable for indoor switchgear — clean, dry environments where dust ingress is minimal. The unit is Category B (selective) per IEC 60947-2, meaning it's designed for full discrimination with downstream breakers, so a fault on a feeder won't take the main bus down.

Rated service breaking capacity and withstand

Ics (service breaking capacity) matches Icu at 55 kA for 220…440 V AC and 42 kA at 690 V AC — that means after one fault interruption at those levels, the breaker is still rated to carry and switch its full load current. Short-time withstand (Icw) is 42 kA for 1 s at 690 V, 55 kA for 1 s at 440 V, and 30 kA for 3 s across the 440/690 V range. That 3-second rating is what lets you coordinate with downstream breakers for selective tripping: the main holds in for a delayed fault while the feeder clears.

Frequently asked questions

Where can I buy the ENW24116 and how do I get a price?

The ENW24116 is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What are the key ratings of the ENW24116?

Rated current 4000 A at 40 °C, breaking capacity 55 kA Icu at 220…440 V AC, rated insulation voltage 1000 V AC, rated operational voltage 690 V AC, all per IEC 60947-2.

What compliance documentation does Schneider provide for the ENW24116?

The breaker complies with IEC 60947-2 and carries a suitability-for-isolation marking per that standard. Specific RoHS/REACH/UL declarations should be requested at quote time.

MPN