Skip to main content
Schneider Electric ENW24121 — Air Circuit Breakers

Schneider Electric ENW24121 EasyPact NW Circuit Breaker, 200

MPNENW24121
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24121, 2000 A at 40 °C, 50 kA Icu at 440 V AC, 4-pole drawout.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24121 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24121 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24121 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24121 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24121 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24121 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24121 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24121 is a 4-pole drawout circuit breaker from the EasyPact NW range, rated 2000 A at 40 °C and built to IEC 60947-2. It breaks 50 kA Icu at 220…440 V AC and 42 kA at 690 V AC — numbers that tell you this thing is sized for main feeders in a distribution board, not branch circuits.

That's rare at this ampacity — most breakers drop Ics below Icu.

Integration notes

Drawout mounting on a rail — the breaker slides into a fixed cradle, so you can rack it out for maintenance without killing the bus. Rear connections, horizontal or vertical orientation. The 4-pole version (ENW24121) has the neutral on the left. IP40 front face keeps fingers out but doesn't seal against hose-down; this is an indoor distribution breaker, not a wet-location disconnect. Mechanical durability: 20,000 cycles with maintenance, 10,000 without — that's a lifetime in a fixed feeder application.

Frequently asked questions

Where can I buy the ENW24121 and get a price?

The ENW24121 is sourced to order against an RFQ through independent distribution. Submit a quote request; availability and current pricing are confirmed at quote time.

What is the closest alternative to the ENW24121 in the same family?

Within the EasyPact NW range, the closest peer is the drawout 4-pole breaker at the same 2000 A frame but with a different breaking capacity code or control voltage. The deciding factor is whether your system requires the full 50 kA Icu at 440 V or can step down to a lower interrupting rating — check the coordination study before swapping.

What compliance documentation does Schneider provide for the ENW24121?

The breaker is certified to IEC 60947-2 and carries a suitability-for-isolation declaration per that standard. Pollution degree 4 per IEC 60664-1 is documented. For RoHS, REACH, and UL documentation, request the manufacturer's declaration of compliance with the RFQ — those are not pre-loaded in the spec record.

MPN
ENW24121