Schneider Electric ENW24123 — Air Circuit Breakers

Schneider Electric ENW24123 EasyPact NW Circuit Breaker, 320

MPNENW24123
Active

Schneider Electric EasyPact NW, air circuit breaker, ENW24123, 3200 A at 40 °C, 4 poles, 50 kA Icu at 440 V AC, drawout mounting, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24123 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24123 — Electrical ratings
ParameterValue
Rated current (In)3200 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24123 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24123 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24123 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24123 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24123 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The ENW24123 is a 3200 A air circuit breaker from the EasyPact NW range, designed for distribution duty in low-voltage switchgear. The 42 kA Icu at 690 V AC covers higher-voltage installations. Rated service breaking capacity Ics matches the Icu values, meaning after clearing a fault at those levels the breaker remains serviceable, not just safe. The drawout mounting (rail-supported) lets you rack the breaker out for maintenance without disturbing the busbars — a standard feature on large air breakers for panel builders.

Deployment context

At 556 mm wide, 439 mm high, and 395 mm deep, this breaker fits into a dedicated drawout cradle in a low-voltage switchboard. The rear connection position (vertical or horizontal) and 115 mm connection pitch without spreader dictate busbar drilling and cable landing layout. The push-button control and contact position indicator give clear local status without opening the door.

Certified to IEC 60947-2 for low-voltage switchgear and controlgear. Suitability for isolation is confirmed, so it can be used as a disconnecting means. The 4-pole version (4P 4d) allows full neutral protection with selectable settings: without protection (3D), 0.5 x Ir (3D + N/2), or 1 x Ir (4D).

Frequently asked questions

What is the breaking capacity of ENW24123?

The ENW24123 has a rated ultimate breaking capacity Icu of 50 kA at 220…440 V AC and 42 kA at 690 V AC, both per IEC 60947-2. The service breaking capacity Ics matches those values, so the breaker remains usable after clearing a fault at those levels.

What is the rated current and voltage for ENW24123?

Rated current In is 3200 A at 40 °C. Rated operational voltage Ue is 690 V AC, and rated insulation voltage Ui is 1000 V AC.

MPN