Skip to main content
Schneider Electric ENW24126

Schneider Electric ENW24126 EasyPact NW Circuit Breaker, 100

MPN ENW24126
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24126, 4P, 1000 A at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, IP40, fixed mounting.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24126 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric ENW24126 is a 4-pole EasyPact NW air circuit breaker rated 1000 A at 40 °C — the continuous current it can carry without derating in a typical 40 °C panel environment. That 1000 A figure is the thermal rating (In), not a short-time or instantaneous pickup; it governs the main bus or feeder it protects. Breaking capacity is 50 kA Icu at 220…440 V AC and 42 kA Icu at 690 V AC, both per IEC 60947-2. The Icu (ultimate breaking capacity) means the breaker can safely interrupt one fault at that level and still be functional afterward — it does not guarantee further service without inspection. Rated operational voltage (Ue) is 690 V AC, and rated insulation voltage (Ui) is 1000 V AC — the latter tells you the internal creepage and clearance are designed for a 1000 V system, even though the breaker is applied at 690 V. That headroom matters for installations where the system voltage may rise or where the breaker sits in a higher-voltage switchgear lineup.

Deployment context and physical integration

This is a fixed-mount breaker on a base plate, not a draw-out or plug-in unit. Dimensions are 537 mm wide × 352 mm high × 297 mm deep — a substantial footprint that needs a dedicated compartment in the switchgear lineup, not a DIN-rail clip. That means it can serve as a disconnecting means for a feeder, satisfying the lockout/tagout requirement without a separate disconnect switch.

Designed and tested to IEC 60947-2, the international standard for low-voltage circuit breakers. This covers the breaking capacity ratings, service duty, and isolation suitability listed above. The pollution degree 4 rating per IEC 60664-1 is an additional environmental classification that goes beyond the base standard.

MPN