Schneider Electric ENW24128 — Air Circuit Breakers

Schneider Electric ENW24128 EasyPact NW Circuit Breaker, 160

MPNENW24128
Active

Schneider Electric EasyPact NW, ENW24128, fixed-mount circuit breaker, 1600 A at 40 °C, 50 kA Icu at 440 V AC, 4P, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24128 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24128 — Electrical ratings
ParameterValue
Rated current (In)1600 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24128 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24128 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24128 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24128 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24128 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24128 is a fixed-mount EasyPact NW circuit breaker rated 1600 A at 40 °C, with a breaking capacity of 50 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. It is a 4-pole device (4P 4d) with rear vertical/horizontal connections and a 115 mm connection pitch without spreader. The IP40 enclosure suits indoor distribution panels where dust and accidental contact are the main concerns — not washdown or outdoor exposure.

Pollution degree 4 per IEC 60664-1 means the internal clearances are designed for conductive dust or heavy condensation environments — a step above the usual PD3 found in commercial gear.

Deployment context

This breaker mounts fixed to a base plate (not DIN rail) with rear connections — typical for large low-voltage switchboards in industrial or utility distribution. The 537 mm width, 352 mm height, and 297 mm depth require a dedicated compartment; plan for busbar and cable entry clearance on the rear side. The push-button control type means manual open/close on the front face, with a contact position indicator for visual status.

Frequently asked questions

How do I get current pricing and availability for ENW24128?

Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront for a current quote on this order code.

What is ENW24128's listed depth?

The depth is 297 mm, with a width of 537 mm and height of 352 mm.

What is ENW24128's range?

It belongs to the EasyPact NW range of low-voltage circuit breakers from Schneider Electric.

What compliance documentation does this brand provide for ENW24128?

The breaker is designed to IEC 60947-2 and carries a pollution degree 4 rating per IEC 60664-1. Specific RoHS/REACH/UL documentation should be requested at quote time — the evidence does not list those certifications directly.

MPN