Skip to main content
Schneider Electric ENW24132 — Air Circuit Breakers

Schneider Electric ENW24132 EasyPact NW Circuit Breaker, 400

MPNENW24132
Active

Schneider Electric EasyPact NW series, ENW24132 4P fixed circuit breaker, 4000 A rated current at 40 °C, 55 kA Icu at 440 V AC, IEC 60947-2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24132 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24132 — Electrical ratings
ParameterValue
Rated current (In)4000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24132 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 55 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2 121 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity55 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24132 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24132 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24132 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24132 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24132 is a 4-pole EasyPact NW fixed-mount circuit breaker rated 4000 A at 40 °C, with a breaking capacity of 55 kA Icu at 220–440 V AC and 42 kA Icu at 690 V AC per IEC 60947-2. The 4000 A CT rating matches the main bus for high-current distribution panels — this is a main breaker, not a feeder or branch device.

The 4000 A rated current at 40 °C ambient is the continuous load it carries without tripping — size your upstream transformer and bus bars for at least this. The IP40 enclosure keeps out tools and wires over 1 mm but is not washdown-rated; install in a dry, lockable enclosure.

Frequently asked questions

What standards does ENW24132 comply with?

It complies with IEC 60947-2 for circuit-breaker performance, with suitability for isolation and pollution degree 4 per IEC 60664-1.

Where can I buy ENW24132 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the mechanical durability of ENW24132?

20,000 cycles with maintenance and 10,000 cycles without maintenance, per IEC 60947-2. Electrical durability is 5,000 cycles at 440 V and 2,500 cycles at 690 V without maintenance.

MPN
ENW24132