Skip to main content
Schneider Electric ENW24133

Schneider Electric ENW24133 EasyPact NW Circuit Breaker, 800

MPN ENW24133
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24133, 3P, 800 A at 40 °C, 66 kA Icu at 440 V AC, drawout, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24133 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24133 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric ENW24133 is an EasyPact NW drawout circuit breaker rated 800 A at 40 °C, with a 66 kA Icu breaking capacity at 220...440 V AC (50/60 Hz) per IEC 60947-2. Three-pole, 3d protected, with a drawout mechanism for racking in and out of the cradle without disturbing the power connections. IP40 enclosure keeps out tools and fingers but not water — install in a dry indoor switchgear lineup.

The H breaking capacity code (66 kA Icu at 440 V) puts this in the high-interrupting tier for its frame size. Service breaking capacity Ics is 65 kA at the same voltage — meaning after clearing a 65 kA fault the breaker is still rated to carry and switch load current, not just a one-shot device. Short-time withstand Icw is 65 kA for 1 s at 440 V, which supports downstream selectivity with other breakers in the same lineup. Rated insulation voltage Ui is 1000 V AC, impulse withstand Uimp is 12 kV — the breaker handles the transient surges common in industrial distribution without flashover.

Dimensions: 441 mm wide, 439 mm high, 395 mm deep. That depth includes the drawout mechanism and arc chutes — measure the enclosure depth to confirm the breaker racks in fully without door interference.

MPN