Skip to main content
Schneider Electric ENW24137

Schneider Electric ENW24137 EasyPact NW Circuit Breaker, 200

MPN ENW24137
Active

Schneider Electric EasyPact NW, ENW24137, 3P drawout air circuit breaker, 2000 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24137 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24137 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

What this 2000 A drawout breaker does on your line

It's built for main distribution duty in industrial switchgear — the kind of breaker that sits between a transformer secondary and a plant's main bus, not a feeder branch. The 66 kA Icu at 440 V AC (50/60 Hz) means it can interrupt a fault current up to that level without failing, and the 50 kA Icu at 690 V AC covers higher-voltage installations. That's Category B utilisation (IEC 60947-2), so it's fully rated for selectivity with downstream breakers — you can coordinate trips so only the faulted section clears, keeping the rest of the plant live. Pollution degree 4 per IEC 60664-1 is the heavy-duty rating — it's designed for conductive dust, condensation, or industrial atmospheres where a standard breaker's creepage distances might track. The 12 kV impulse withstand voltage (Uimp) backs that up for surge environments like large motor starts or nearby lightning.

Durability and service intervals

Mechanical durability is 20,000 cycles with maintenance and 10,000 without per IEC 60947-2 — that's a long service life for a main breaker that might operate a few times a year. Electrical durability is 6,000 cycles at 440 V and 4,000 at 690 V without maintenance. The 25 ms maximum breaking time is fast enough for most coordination schemes. IP40 protection means it's splash-proof against tools and fingers but not water — keep it indoors or in a weatherproof enclosure.

MPN
ENW24137