Schneider Electric ENW24150

Schneider Electric ENW24150 EasyPact NW Circuit Breaker, 100

MPN ENW24150
Active

Schneider Electric EasyPact NW, air circuit breaker, ENW24150, 1000 A at 40 °C, 66 kA Icu at 440 V AC, 4 poles, drawout mounting, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24150 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24150 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric ENW24150 is an EasyPact NW air circuit breaker rated for 1000 A at 40 °C, with a breaking capacity of 66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. It is a 4-pole drawout unit with rear connections, designed for distribution applications in industrial switchboards.

The H breaking capacity code (66 kA Icu at 440 V) positions this breaker for high-fault installations where upstream coordination demands a robust interrupting rating. At 690 V the Icu and Ics both drop to 50 kA, still adequate for most 690 V distribution boards.

Drawout mounting on a rail support with a 115 mm connection pitch (without spreader). Rear horizontal or vertical connection positions. Neutral on the left. Pollution degree 4 per IEC 60664-1 — suitable for harsh industrial environments with conductive pollution. IP40 enclosure protection; install in a switchboard with a higher overall IP rating if washdown or dust ingress is a concern.

Electrical endurance and duty

Category B utilisation (selective coordination capable). Electrical durability: 6000 cycles at 440 V AC without maintenance, 4000 cycles at 690 V AC. Mechanical durability: 20000 cycles with maintenance, 10000 without. Maximum breaking time 25 ms, closing response 70 ms. Suitability for isolation confirmed per IEC 60947-2 — the contact position indicator gives visual confirmation of open contacts.