Skip to main content
Schneider Electric ENW24153 — Air Circuit Breakers

Schneider Electric ENW24153 EasyPact NW Circuit Breaker, 200

MPNENW24153
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24153, 2000 A at 40 °C, 66 kA Icu at 440 V AC, 4P, drawout mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24153 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24153 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24153 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24153 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24153 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24153 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24153 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24153 is an EasyPact NW drawout circuit breaker rated 2000 A at 40 °C with a breaking capacity of 66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC — both conforming to IEC 60947-2.

Drawout mounting and panel integration

The ENW24153 uses a drawout mounting mechanism on a rail, which means the breaker chassis stays wired to the bus while the moving portion can be racked out for maintenance or replacement without de-energizing the entire switchboard — a standard practice for high-current distribution where downtime costs are high. The 4-pole configuration with neutral on the left and rear connection positions suits fixed-pattern switchgear layouts where busbar runs are pre-drilled.

Electrical durability and duty cycle

Rated for Category B utilization, the ENW24153 delivers 6000 electrical cycles at 440 V without maintenance and 4000 cycles at 690 V. Mechanical durability is 20000 cycles with maintenance, 10000 without. The 25 ms maximum breaking time and 70 ms maximum closing response are fast enough for most distribution protection schemes, but if you need arc-flash mitigation below those thresholds, verify coordination with your upstream relay settings.

Insulation and environmental limits

Rated insulation voltage (Ui) is 1000 V AC, and operational voltage (Ue) is 690 V AC — both at 50/60 Hz. Storage temperature range is -40...85 °C without the control unit, -25...85 °C with it; operating range is -5...60 °C.

Frequently asked questions

What is the breaking capacity of ENW24153?

66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. The Ics (service breaking capacity) is 65 kA at 440 V and 50 kA at 690 V.

Where can I buy ENW24153?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What standards does ENW24153 comply with?

IEC 60947-2 for circuit-breaker performance, and IEC 60664-1 for pollution degree 4 insulation coordination. Suitability for isolation is confirmed per IEC 60947-2.

MPN
ENW24153