Skip to main content
Schneider Electric ENW24155 — Air Circuit Breakers

Schneider Electric ENW24155 EasyPact NW Circuit Breaker, 320

MPNENW24155
Active

Schneider Electric EasyPact NW, ENW24155, drawout circuit breaker, 4P, 3200 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24155 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24155 — Electrical ratings
ParameterValue
Rated current (In)3200 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24155 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24155 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24155 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24155 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24155 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

What the 3200 A rating means for your main distribution board

The ENW24155 is a 4-pole drawout air circuit breaker from the EasyPact NW range, rated 3200 A at 40 °C ambient. The drawout mounting means the breaker chassis slides out of its cradle for inspection or replacement without disturbing the bus connections, which cuts downtime on a line-down event. Breaking capacity is 66 kA Icu at 220…440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. The Ics (service breaking capacity) is 65 kA at 440 V, meaning it can clear that fault level repeatedly without needing replacement, which matters for coordination studies.

Pollution degree 4 — what it changes

Rated pollution degree 4 per IEC 60664-1 means the breaker is designed for environments where conductive pollution (dust, moisture, condensation) is present and the insulation system must tolerate continuous exposure. This is the standard rating for open-air switchgear in industrial halls — not a clean-room or climate-controlled panel. The IP40 enclosure (finger-safe, no water protection) is consistent with indoor switchgear installation; if the board is in a washdown area, you need an outer enclosure.

Integration into the switchboard

Mounting is drawout on a rail support, with rear vertical/horizontal connection positions. The neutral sits on the left side (4P 4d protected poles). Connection pitch is 115 mm without a spreader — that dimension governs busbar drilling and busway alignment in the switchgear. Dimensions: 556 mm wide, 439 mm high, 395 mm deep.

Frequently asked questions

How do I get current pricing and availability for ENW24155?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does ENW24155 carry?

The breaker is designed and tested to IEC 60947-2, with isolation suitability confirmed per that standard. Pollution degree 4 per IEC 60664-1. No RoHS/REACH/UL statements appear in the listing, but IEC 60947-2 is the governing standard for LV switchgear in most markets.

What is ENW24155's breaking capacity at 440 V?

66 kA Icu (ultimate) and 65 kA Ics (service) at 220…440 V AC, 50/60 Hz. At 690 V it derates to 50 kA Icu and 50 kA Ics.

MPN